RAY-BAR Lead Backed Drywall Specifications
Section 09250 Gypsum Board
1.01 SUMMARY
A. Lead Sheet: In compliance with Federal Specification QQ-L-201f, Grade C, 99.9% pure, and ASTM B749, Type L51121. Thickness as indicated on Lead Protection Schedule and Comply with lead shielding equivalents as specified by the qualified health radiation physicist report for this particular project. Note: 7’0” is minimum lead height per national standard unless otherwise indicated.
A. Standards: Comply with requirements of the National Council on Radiation Protection and Measurements (NCRP) Report No. 49“ Structural Shielding Design and Evaluation for Medical Use of X-Rays and Gamma Rays of Energies up to 10 MeV”, and NCRP Report No. 147 “Structural Shielding Design for Medical X-Ray Imaging Facilities”.
B. Comply with lead shielding equivalents as specified by the qualified health radiation physicist report for this particular project.
C. Must Comply with requirements of local regulatory agencies where standards and criteria exceed NCRP Reports 49 and 147.
Lead Backed Drywall must meet or exceed the following specifications or standards:
QQ-L-201f, Grade C, 99.9% Pure – Federal Specification, Lead
ASTM B749 Type L51121, American Society for Testing and Materials- Lead Sheet
ASTM C 36, American Society for Testing and Materials – Gypsum Wall Board, Type “X”
1.03 RELATED DOCUMENTS
1.04 SUBMITTALS
1.04 DELIVERY, STORAGE AND HANDLING
2.01 APPROVED MANUFACTURERS / SUPPLIERS
Ray-Bar Engineering Corporation, Phone (626) 969-1818 or Toll Free (800) 567-XRAY (9729) · Fax (626) 969-6510, www.raybar.com, e-mail sales@raybar.com, a recognized manufacturer regularly engaged in the successful production of the x-Ray Protection Materials specified herein.
2.02 MATERIALS
A. RAY-BAR lead backed drywall is furnished as 5/8”. Fire code gypsum board, with lead meeting Federal Specification QQ-L-201f, Grade C, 99.9% Pure, and ASTM B749, Type L51121, factory laminated under pressure to the backside of the gypsum panel.
* Lead backed plywood also available.B. Fire-rated lead backed drywall (Type RB-LBG) available as U.L. Classified to U.S. and Canadian Safety Standards (See complete marking on product must to be utilized at any fire rated lead lined partitions (such as partition design U430) and must identified with proper yellow U.L Label laminated on actual lead side indicating shielding material manufacturer and current fire resistance listing and U.L. classification per the current U.L. certification directory and as tested in accordance with the standard fire test of building construction and materials per ANSI / UL263 (ASTM E119, NFPA 251). There are absolutely no substitutions allowed.
2.03 ACCESSORIES AND FASTENERS
2.04 QUALITY ASSURANCE
A. Fabricator Qualifications: Fabricator / Manufacturer shall be experienced in, equipped for and insured for fabrication equal to standards specified herein. The fabricator shall furnish evidence of Manufacturer having not less than ten (10) years experience in successful fabrication of radiation protection materials similar to products specified herein.
1. Fabricator shall furnish proof of insurance certifying Fabricator is specifically insured in the fabrication of X-Ray Protection / Radiation Shielding Materials.
Single source responsibility: Provide X-Ray Protection Materials and accessories produced as standard products of Ray-Bar Engineering Corporation, Toll Free (800) 567-XRAY (9729) · Phone (626) 969-1818 · Fax (626) 969-6510, www.raybar.com · Email: sales@ Raybar.com, a recognized manufacturer regularly engaged in the successful production of X-ray Protection Materials as specified herein.
PART 3 – EXECUTION
A. Apply gypsum board vertically with long edges parallel to supports and lead lining facing supports and lead lining facing supports. Provide blocking at end joints. Install lead strips minimum 1-1/2 inches wide and same height and thickness as gypsum board lead lining to inside of face of supports and blocking where all vertical joints, inside and outside corners occur. Secure lead batten strips to studs, lead shielding thickness and height as specified in the health radiation physicist report for this project. No untrained persons or trades to occupy room or work area during any lead material installation per Federal OSHA requirements.
B. Secure gypsum board to supports with fasteners spaced as recommended by board manufacturer. Drive fasteners slightly below exposed surface and shield with either lead discs , tabs or internally with 2” wide batten strips, or simply 1-1/4” long steel screws when appropriate per NCRP Report No. 147 and specifically approved by project physicist of record.
C. No other trades or persons to occupy room or work area during installation.
D. All lead trimmings must be recycled or disposed of in compliance with applicable health, safety and environmental codes and regulations. Properly clean up and disposal or recycle all sheet lead trimmings and debris. Never dispose of lead materials in general trash or refuse
E. Refer to Section 09250 for joint treatment and preparation for taping and finishing.
3.02 INSTALLATION OF LEAD BACKED DRYWALL AT CEILINGS
A. Lead backed 5/8” drywall to be installed on ceiling areas when required to provide shielding for occupancy above on areas where appropriate and indicated on plans per shielding report provided by physicist of record for project. All penetrations and joints between lead backed drywall sheets are to be properly shielded with same techniques as on wall partitions.
B. No other trades or persons to occupy room or work area during installation of lead backed drywall in ceilings.
C. All lead trimmings must be recycled or disposed of in compliance with applicable health, safety and environmental codes and regulations. Properly clean up and disposal or recycle all sheet lead trimmings and debris. Never dispose of lead materials in general trash or refuse
D. Refer to Section 09250 for joint treatment and preparation for taping and finishing.
3.03 CERTIFICATION
Upon completion of material, manufacturer shall supply a certificate of compliance stating that all materials have been produced in accordance with this specification. Contractor / Installer shall supply a certificate of compliance stating that all materials have been installed in accordance with this specification, the project plans and the physicist shielding report for this particular project.
3.04 TESTING
After the X-RAY equipment has been installed and placed in operating condition and prior to use, radiation shielding will be tested by original project radiation physicist or record at owner’s expense